Two Control Philosophies on One Pipe Circuit
Smart thermostatic radiator valves (TRVs) are among the most popular add-ons to a domestic heating system. They allow each room to be scheduled and set back individually, they respond to occupancy and open windows, and they promise savings by ensuring that no room is heated more than necessary. The logic behind them was developed in the era of the fossil-fuel boiler, where the heat source is a robust, high-temperature, low-volume appliance which can tolerate wide swings in system flow, and where closing a radiator simply reduces the load on a boiler that will in any case modulate or cycle with minimal penalty.
An air-source heat pump is a different kind of heat source. Its efficiency depends on delivering heat at the lowest possible flow temperature, across a narrow temperature differential, with a steady and continuous flow of water through the condenser. The refrigeration cycle is a delicate balance of pressures, temperatures, oil return and inverter loading that is easily disturbed by changes in the water-side conditions. When the independent zone logic of smart TRVs is layered on a heat pump circuit with no regard to the hydraulic consequences, the two control philosophies come into conflict, and the interface at which they collide is the pump, the pipework and the plate heat exchanger. This audit deconstructs that conflict, from the valve orifice equation to the compressor cycle, quantifies it with a worked example, and sets out the architectural solutions.
Choked Flow and Valve Orifice Fluid Mechanics
The flow through a restriction such as a valve is described by the orifice relationship Q = Cd × A × (2ΔP / ρ)1/2, in which Q is the volumetric flow rate, Cd a discharge coefficient, A the open area, ΔP the pressure drop and ρ the fluid density. In HVAC practice this is condensed into the valve flow coefficient, Kv, defined as the flow in cubic metres per hour of water that produces a pressure drop of one bar across the valve: Q = Kv × (ΔP / ρrel)1/2, with ΔP in bar and ρrel the density relative to water. The important feature is that flow is proportional to the square root of the pressure drop, or equivalently that pressure drop is proportional to the square of the flow: ΔP = (Q / Kv)2.
The behaviour of a branched circuit follows from the rules for combining resistances. Elements in series add their resistances, which are proportional to 1 / Kv2, so that 1 / Kv,total2 = sum of 1 / Kv,i2. Elements in parallel add their flow coefficients directly: Kv,total = sum of Kv,i. A radiator circuit with a number of parallel branches, each of which has a TRV, therefore has a collective hydraulic aperture equal to the sum of the apertures of the branches. When a smart TRV closes, in whole or in part, the Kv of its branch falls towards zero, and the collective aperture of the distribution circuit falls with it.
A Worked Example
Take an 8 kW heat pump serving eight radiator branches, with a design temperature differential of 5 K. The design flow is 8,000 / (4,180 × 5) = 0.383 kg/s, which is approximately 1.38 m3/h. Let each open branch, comprising the TRV, the radiator and its pipework, have a Kv of 0.9, so that the eight open branches together present a Kv of 7.2 and a pressure drop at design flow of (1.38 / 7.2)2 = 0.037 bar, or 3.7 kPa. Let the remaining part of the circuit, in series with the distribution, which includes the heat pump plate heat exchanger and the main pipework, have a Kv of 3.1, giving a pressure drop of 20 kPa at design flow. The total system pressure at design flow is therefore approximately 23.7 kPa, and a circulator set to deliver that pressure in constant-pressure mode will deliver the design flow with all branches open.
Now let the smart TRVs close branches while the pump continues to deliver 23.7 kPa. With four branches open the distribution Kv is 3.6, the system Kv is 2.35, and the flow is 2.35 × (0.237)1/2 = 1.14 m3/h, or 83% of design. With two branches open the distribution Kv is 1.8, the system Kv is 1.56, and the flow is 0.76 m3/h, or 55%. With one branch open the distribution Kv is 0.9, the system Kv is 0.86, and the flow is 0.42 m3/h, or 30%. In the last case the pressure drop across the single open branch has risen from 3.7 kPa to 21.8 kPa, a sixfold increase, with almost the whole pump head now dropped across the distribution. The system operating point, the intersection of the pump curve and the system resistance curve, has moved to a region of low volume and high pressure in the distribution.
The rise in the differential pressure across the open valves has a second consequence in the form of noise. The velocity through a throttled orifice is proportional to the square root of the pressure drop, and manufacturers of TRVs typically specify a maximum differential pressure of the order of 0.2 to 0.6 bar, with noise problems appearing at lower values when the valve is close to its seat. A smart TRV operating close to its closed position, as a modulating motor does when it throttles to maintain a room temperature, has a small flow area, a high velocity and a high propensity for whistling and hissing as the differential pressure rises. The problem is made worse by the mechanism of progressive closure: it is the partly-closed valve that is noisiest.
Pump Head, Cavitation Metrics and Pump Stress
A variable-speed circulator is designed to cope with changes in system resistance. Its control modes are constant pressure, in which the speed is varied to hold a fixed head, proportional pressure, in which the head setpoint falls linearly with flow, and fixed speed. The pump affinity laws describe the speed dependence: the flow is proportional to the speed, the head to the square of the speed, and the power to the cube. In proportional-pressure mode, the pump follows a line that reduces the head as the flow falls, and so tends to moderate the rise in distribution differential pressure. In constant-pressure mode, as assumed above, the head is maintained and the full pressure falls on the distribution. In fixed-speed mode the pump moves up its characteristic curve to a higher head as the flow falls, so that the pressure in the distribution rises still further. The choice of mode is therefore consequential for a system with active TRVs, and the manufacturer's recommendation for radiator systems is generally proportional pressure.
What Cavitation Requires
The dangers to the pump of low flow are often summarised as cavitation, and the topic needs careful treatment. Cavitation occurs when the local static pressure in the liquid falls below its vapour pressure, so that vapour cavities form and subsequently collapse violently when carried into regions of higher pressure, eroding the impeller and producing a characteristic rattling noise. The criterion is expressed through the net positive suction head: NPSHavailable = (ps − pv) / (ρg) + v2 / 2g, where ps is the absolute static pressure at the pump inlet, pv the vapour pressure at the fluid temperature and v the inlet velocity. Cavitation begins when the NPSH available falls below the NPSH required by the pump at its operating point.
The numbers for a heat pump circuit are generally favourable. A sealed heating system is charged to a cold pressure of the order of 1 to 1.5 bar gauge, which is approximately 200 to 250 kPa absolute. The vapour pressure of water at a typical heat pump flow temperature of 45 degrees Celsius is approximately 9.6 kPa, and at 55 degrees Celsius approximately 15.8 kPa, so that the pressure margin is of the order of 190 kPa or more, equivalent to roughly 19 metres of head, against the NPSH required by a domestic circulator, which is of the order of 0.5 to 2 metres. By contrast, a boiler circuit at 80 degrees Celsius, where the vapour pressure is 47 kPa, has a much narrower margin. On this basis, true cavitation in a correctly pressurised heat pump circuit is a lower-probability failure than is sometimes asserted.
It can nevertheless occur, and the conditions are specific. If the system is under-pressurised, because of a leak, an expansion vessel with a lost charge or an incorrect initial fill, the margin shrinks. If the expansion vessel is connected on the discharge side of the pump, or at a point from which the pressure loss to the pump inlet is significant, then a restriction between the vessel and the pump inlet reduces the inlet pressure. Where the pump is located on the return leg and the return pipework is long and throttled, the suction pressure is lower than the static pressure at the vessel by the pressure drop between them. Dissolved air released from the water at reduced pressure forms bubbles that behave like a cavitation phenomenon, producing noise and a loss of pumping capacity, though with a different mechanism. The remedy lies in correct system pressurisation, in locating the expansion vessel on the pump suction side, and in the removal of air.
Low-Flow Stress and Ohmic Heating
The more realistic stress on the pump at low flow is thermal rather than hydraulic. Most domestic circulators are wet-rotor machines, in which the rotor runs in the pumped fluid, and the fluid also cools the stator can and the bearings. When the flow is reduced the fluid in the pump housing is renewed less rapidly, and the heat produced by the motor losses and by hydraulic dissipation, which at the shut-off point is converted wholly to heat in the fluid, raises the local temperature. For a small pump drawing 20 to 40 W at low flow, the temperature rise in a circuit with a volume of tens of litres is slow, but the pump housing itself, with a few hundred millilitres, can run noticeably warmer than the system. The electronics of an ECM pump, which are cooled by the fluid or by air, have their own thermal limits, and sustained operation at the extremes of the operating range shortens life. The ohmic losses in the stator windings are proportional to the square of the motor current, which at a given speed falls with load, so that at low flow the copper losses are lower, not higher, than at design flow. The conclusion is that the thermal risk of low-flow operation is modest for a pump in a well-designed circuit, and that its principal effects are noise, vibration at the recirculation instability that occurs near shut-off, and wear.
The most serious consequence of reduced flow is therefore not the pump failure but the starvation of the heat pump itself.
Compressor Short-Cycling Kinetics and COP Degradation
An air-source heat pump is rated for a minimum water flow, specified by the manufacturer, at which the plate heat exchanger can transfer the condensing heat without the flow becoming laminar and fouling the plate, and without the exit water temperature exceeding the limit set by the refrigerant pressure. This minimum is commonly of the order of 50% to 70% of the nominal flow, and the unit is fitted with a flow sensor or switch that locks out the compressor if the flow falls below it. In the example above, a minimum flow of 50% of design corresponds to 0.69 m3/h, which is exceeded with two branches open and violated with one. A smart TRV system that closes all but one radiator will therefore starve the heat exchanger.
The chain of consequences proceeds as follows. As the flow drops while the compressor continues to deliver heat, the temperature differential across the condenser rises, because ΔT = Q / (ṁ × c). A unit delivering 8 kW at 30% of the design flow would produce a ΔT of approximately 16 K in place of 5 K. The return water is cooler, but the leaving water rises, and the condensing pressure follows the leaving temperature. The high-pressure protection or the leaving-water temperature limit operates, and the controller either throttles the compressor or stops it. The more usual outcome, where the compressor is an inverter-driven scroll with a minimum modulation limit, typically 20% to 30% of the rated capacity, is that the heating demand of the one open room is below the minimum output of the compressor. The unit then cannot match its output to the load by modulation and must turn on and off, cycling around the setpoint.
The Penalties of Cycling
The penalties of short-cycling are physical and thermodynamic. At each start the compressor must establish the pressure difference between the condenser and the evaporator, which requires several tens of seconds to minutes, during which the system is not operating at its steady-state efficiency, and the compressor motor draws a start-up current. During the off period the refrigerant pressures equalise and the energy stored in the hot side of the circuit is dissipated, to be re-established at the next start. Oil is carried out of the compressor with the refrigerant and must return, which requires a minimum running time, and compressor manufacturers specify a minimum run time of the order of 3 to 5 minutes and a maximum number of starts per hour, typically 6 to 10. Frequent starts increase the wear on the scroll tips and bearings, and the stress on the inverter's power electronics and DC link capacitors by repeated inrush and thermal cycling.
The effect on efficiency is recognised in the standards for rating heat pumps. In EN 14825, which defines the calculation of seasonal performance, a degradation coefficient with a default value of 0.9 is applied to the part-load performance of units that cycle on and off, representing a loss of 10% at low load factors, and measured field cycling losses can be larger. The condensing temperature also influences the coefficient of performance: as a rule of thumb the COP changes by 2% to 3% per kelvin of change in the flow temperature, so that a few kelvin of overshoot in the leaving water temperature at each start costs a further several percent. Defrost cycles, which draw heat from the water to melt frost on the evaporator, add to the problem if the volume of water in the system is too small to supply them without a severe drop in temperature. A defrost lasting three minutes at an effective 6 kW consumes approximately 1.1 MJ, which, if supplied by 50 litres of water, lowers its temperature by 5 K, but by 25 K if supplied by only 10 litres.
The minimum system volume to prevent short-cycling can be estimated from the energy balance. For a minimum run time tmin and a permitted swing ΔTsw in the system temperature, the required volume is V = Qmin × tmin / (c × ρ × ΔTsw). For a minimum compressor output of 2.5 kW, a run time of 5 minutes (300 s) and a swing of 5 K, this gives V = 2,500 × 300 / (4,180 × 5), or approximately 36 litres. An 8 kW unit feeding eight small radiators and microbore or small-bore pipework may have a total water content below this, and when most of the radiators are closed by the TRVs the volume that is effectively in circulation is smaller still, which is a further reason why zone closures bring on cycling. The effect on the seasonal coefficient of performance (SCOP) is substantial: a system that would achieve a SCOP above 3.5 under steady operation can fall to below 3.0 when it cycles throughout the shoulder seasons, which is when the load is lowest and the TRVs are closed most of the time.
| Hydronic Distribution Architecture | Index Circuit Flow Volumetric Stability | System Delta-P Curve Profile | Pump Cavitation and Ohmic Stress Vector | Realised Seasonal Coefficient of Performance (SCOP), indicative |
|---|---|---|---|---|
| Rigid micro-zoned smart TRVs on every radiator, no bypass | Poor: flow falls to 83%, 55% and 30% of design as 4, 2 and 1 branches remain open; below the typical minimum flow when 1 branch is open | Steep: distribution differential pressure rises from 3.7 kPa to 21.8 kPa with one branch open; TRV noise | Low true-cavitation risk when correctly pressurised; elevated risk if under-pressurised or vessel misplaced; low-flow thermal and vibration stress; flow lockouts at the heat pump | Approx. 2.6 to 3.1, with cycling and degradation of 10% or more |
| Smart TRVs with an automatic differential bypass valve (ABV) | Fair to good: bypass maintains minimum flow through the heat pump | Capped: differential pressure limited to the ABV setting, commonly 0.2 to 0.4 bar | Reduced: pump operates nearer its design point; heat pump protected from flow starvation | Approx. 3.0 to 3.5; bypassed hot water raises the return temperature and costs efficiency |
| Open weather-compensated base-load circuit (index rooms with no TRV or TRVs held to a minimum opening; smart TRVs for set-back only) | Good: a guaranteed minimum aperture holds flow above the minimum at all times | Flat: operating point stays close to design | Minimal | Approx. 3.5 to 4.1 under steady, low-temperature operation |
| Low-loss header with variable secondary (TRVs free to throttle) | Good on the primary side: constant heat pump flow regardless of secondary demand | Decoupled: primary and secondary pumps operate independently | Minimal on the primary; the secondary pump operates at reduced flow | Approx. 3.2 to 3.8; mixing at the header raises the primary return temperature |
| Open base-load circuit plus buffer vessel (hybrid) | Very good: buffer volume absorbs transients and supports defrost | Flat to decoupled depending on buffer arrangement | Minimal | Approx. 3.6 to 4.2 where the buffer is sized to prevent cycling |
The SCOP ranges in the matrix are illustrative planning figures for a correctly sized unit at flow temperatures of 35 to 45 degrees Celsius, not measurements of particular installations. They are intended to show the relative ordering and the approximate size of the penalty. The flow percentages and pressures are drawn from the worked example, which assumes the stated Kv values and a constant-pressure pump setting.
Systematic Volumetric Engineering Workarounds
The hydraulic remedies fall into two groups. The first preserves a minimum flow through the heat pump by providing an alternative path for water when the radiator circuit closes. The second separates the heat pump circuit from the distribution so that the two operate at independent flow rates. A third approach, which is the cheapest, addresses the control logic.
Automatic Bypass Valves
An automatic differential bypass valve (ABV) is a spring-loaded valve connected between the flow and the return, close to the heat pump or pump. It remains closed while the differential pressure between the two is below its setting, and opens progressively as the differential pressure rises above it, passing water from the flow directly to the return. In effect it is a variable resistor in parallel with the distribution that opens as the TRVs close, and so it limits the rise in pressure and holds up the flow through the heat pump. The setting should be higher than the design pressure drop across the distribution and radiators, with a margin, so that it does not open at design flow, and lower than the maximum permitted TRV differential pressure. In the worked example, the distribution drop at design flow is 3.7 kPa, and a setting of 10 to 15 kPa would hold the pressure across the TRVs within a tolerable range while passing the surplus. Commissioning requires measurement, not estimation, since the setting is adjustable and the correct value depends on the actual pressure.
The ABV has an unavoidable thermodynamic cost. The water that passes through the bypass has not given up its heat to the rooms, and when it mixes with the cooler return it raises the return temperature to the heat pump. If a fraction f of the primary flow is bypassed, the return temperature seen by the heat pump is approximately Tret,sec + f × (Tflow − Tret,sec). With a flow temperature of 40 degrees Celsius, a secondary return of 35 degrees Celsius and a bypass fraction of 45%, which corresponds to the circuit with two branches open, the return temperature is 37.3 degrees Celsius, the effective temperature differential across the heat pump falls from 5 K to 2.7 K, and by the 2% to 3% per kelvin rule the efficiency declines by about 5% to 7%. The ABV is therefore a valid protective measure but should be regarded as a last line of defence and not as the principal means of control.
Low-Loss Headers and Hydraulic Separation
A low-loss header, or hydraulic separator, decouples the primary circuit of the heat pump from the secondary circuit of the distribution. The header is a vessel with a large cross-section, typically sized for an internal velocity of 0.1 to 0.2 m/s, in which the pressure difference between the flow and return connections is negligible. The primary pump circulates a constant flow through the heat pump and the header, and the secondary pump circulates a variable flow between the header and the radiators. When the TRVs close and the secondary flow falls, the surplus primary flow passes through the header from flow to return, and the heat pump continues to see its design flow. The principle is the same as for the microbore case discussed elsewhere in this series, and the same trade-off applies: the surplus flow recirculates, raising the primary return temperature. The effective design rule is that the primary flow should not exceed the maximum secondary flow, and that the secondary pump should be of the variable-speed type, operating in proportional-pressure mode.
Buffer Vessels
A buffer vessel is a store of hot water in the circuit. In a parallel configuration it is connected as a hydraulic separator and a thermal store. In a series configuration, all the flow passes through it. Its function in the present context is to supply water volume, which prevents short-cycling by lengthening the on-time of the compressor and by supplying the energy needed for defrost. The sizing follows the energy balance given above, and a figure of the order of 10 to 20 litres per kilowatt of heat pump capacity is commonly used as a first approximation, with the manufacturer's minimum system volume taking precedence. A buffer does not cure the problem of minimum flow, and is complementary to the bypass or the header, not a substitute.
Control-Level Remedies
The cheapest and often the most effective remedy lies in the configuration of the smart TRVs themselves. The principal guidance is to preserve a minimum hydraulic aperture. The requirement can be expressed as a constraint on the sum of the open flow coefficients: the collective Kv of the open branches must be at least that required to pass the heat pump minimum flow at the available pump pressure. For the worked example, with a minimum flow of 0.69 m3/h and a pump pressure of 23.7 kPa, the system Kv must be at least 0.69 / (0.237)1/2 = 1.42, and with the fixed part of Kv of 3.1, the distribution must have a Kv of at least 1.6, which is about two of the eight branches. In practice this means that at least a defined set of index rooms, often the bathroom, the hall and the landing, should be left without a TRV or with a TRV that is held at a minimum opening, and that the smart system should use setback rather than full closure in the remaining rooms, with a minimum valve opening of, for example, 20% to 30%. A smart TRV system that can be configured with such limits, and that exposes the total demand to the heat pump controller by OpenTherm or another protocol so that the flow temperature is modulated with demand, is better suited to a heat pump than one that closes valves independently.
The mode of the circulator should be matched to the system. For a radiator system with TRVs, proportional-pressure control is generally recommended, and for underfloor heating, constant pressure. The pump setting should be verified by measurement of the differential pressure and flow at commissioning in the worst-case condition, with all but the index branches closed.
Specification Guidance for Practitioners
The analysis suggests the following approach for installers and automation specifiers. First, treat the heat pump's minimum flow, from the manufacturer's data, as a hard constraint on the control system, and compute the minimum aperture that is required to meet it. Second, define the index circuit explicitly, with radiators that are never fully closed, and configure the smart TRVs to respect minimum opening limits and to operate in setback mode in these rooms. Third, set the pump mode and head by measurement, and fit an automatic bypass valve as a safeguard if the system can be closed down by the user to below the minimum flow, with the setting commissioned and recorded. Fourth, provide the system volume that is needed to prevent short-cycling and to support defrost, by a buffer vessel or a low-loss header with sufficient volume if the circuit alone is too small. Fifth, ensure that the system is correctly pressurised, that the expansion vessel is on the suction side of the pump and that air is removed.
Finally, the efficiency of the whole assembly should be judged at the system level. A set of smart TRVs may save energy in a boiler system by reducing the heat delivered to unoccupied rooms, but in a heat pump system the same actions, if they produce short-cycling and a high return temperature, can cost more in efficiency than they save in heat. The benefit of room-level control is real, and can be captured when the hydraulic architecture is designed to accommodate it; the objective is not to abandon the smart TRV but to place it within a circuit that respects the physics of the heat pump.